Full specification

Model Polaris BP  
   
Capacity 10KVA to 80kva
   
input  
Voltage 208~478 Vac
frequency range 40~70 hz
phase 3 phase/4wires + ground
power factor ≥ 0.99
Current harmonic ≤ 3 (100% non-linear load)
   
output  
phase 3 phase/4wires + ground
Voltage 380 / 400 / 415
voltage precision ± 2%
crest factor 3:1
overload capacity load = 110%, 60 min. ≤ 110%, last 10 min. ≤ 150%, last 1 min. ≤ 150%, shut down ups inmediately
output frecuency utility mode ± 1%, ± 2%, ± 4%, ±5%, ±10% of the rated frecuency (opcional)
output frecuency battery mode (50/60±0.2) hz
thd ≤2% with linear load - ≤5% with non linear load
   
battery  
voltage ±192V / ±204V / ±216V / ±228V / ±240V DC; battery quantity (opcional)
charge current (ups module) maximum current 6A
backup time depends on the capacity of external batteries
   
environment  
temperature 0ºC ~ 40ºC
humidity 0 ~ 95% non condensing
storage temperature -25ºC ~ 55ºC
altitude < 1500m