Model Polaris BPM 150 |
|
|
|
Capacity |
50~150K/50~150K -- 50~200K/50~200K -- 50~300K/50~300K -- 50~400K/ 50~400K -- 50~500K/50~500K -- 50~600K/50~600K |
|
|
input |
|
Nominal voltage |
380/400/41 SVac, (3Ph+N+PE) |
Operating voltage range |
138~305Vac Linear derating; 305~485Vac for 100% Load; |
Operating frequency range |
40Hz-70Hz |
Power factor |
≥ 0.99 |
Harmonic distortion (THDi) |
3% (100% linear load) |
Bypass voltage range |
Max. voltage:220V: +250/o(optional + 10%,+ 15%,+20%); 230V: +20%(optional + 10%,+ 15%) ;240V: + 15%(optional + 10%) Min. voltage: -45% (optional-10%, -20%,-30%) |
Bypass Frequency range |
Frequency protection range: ±10% |
Generator input |
Support |
|
|
output |
|
Rated voltage |
380/400/41 SVac, (3Ph+N+PE) |
Power factor |
1 |
Voltage regulation |
±1% |
Output frequency Line Mode |
±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) |
Output frequency Bat. Mode |
(50/60±0.1 %)Hz |
Crest factor |
3:1 |
Harmonic distortion (tdh) |
≤ 1 % with linear load / ≤4% with non linear load |
Efficiency |
96,5% |
|
|
battery |
|
Battery voltage |
Optional Voltage: ±180V/±192V/±204V/±216V/±228V/±240Vdc/±252Vdc/±264Vdc/±276Vdc/±288Vdc/±300Vdc (30/32/34/36/38/40/42/44/46/48/S0pcs) |
Charge Current(A) UPS cabinet BPM150 Models150k/200K/300k/400k/500k/600k |
60A (Max.) / 80A (Max.) / 120A (Max.) / 160A (Max.) / 200A (Max.) / 240A (Max.) |
Charge Current(A) HPM module |
20A (Max.) |
|
|
SYSTEM FEATURES |
|
Transfer time |
Utility to Battery : 0ms; Utility to bypass: 0ms |
Overload Line Mode |
110% for 60 min., 125% for 1 0min., 150% for 1 min, then transfer to bypass |
Overload Bypass Mode |
≤135%@ ≤ 30șC or 125%@ ≤ 40șC:continuously, 1000% for 1 00ms, then shut down |
Overheat |
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately |
Low battery voltage |
Alarm and Switch off |
Self-diagnostics |
Upon Power On and Software Control |
EPO (optional) |
Shut down UPS immediately |
Battery |
Advanced Battery Management |
Noise suppression |
Complies with EN62040-3 |
Audible & Visual alarms |
Line Failure, Battery Low, Overload, System Fault |
Status LED & LCD display |
Line Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault |
Reading on the LCD display |
lnput,Output, Battery, Command, Setting,Maintenace |
Communication interface |
CAN, RS485,NET, Parallel, Dry contact port, Relay card (optional), SNMP card(optional),Battery temperature sentor (optional) |
|
|
ENVIRONMENTAL |
|
Operating temperature |
0ºC ~ 40ºC |
Storage temperature |
-25ºC ~ 55ºC |
Humidity range |
0 ~ 95% (non condensing) |
Altitude |
<1500m |
Noise level (from 1M distance) |
<63dB / <65dB /<68dB / <70dB |
|
|
PHYSICAL |
|
Dimension WxHxD (mm) UPS cabinet (SM) |
600x1200x850 / 600x1600x850 / 600x2000x850 / 600x2000x850 / 1200x2000x850 / 1400x 2000x850 |
Dimension WxHxD (mm) UPS cabinet (FM) |
1200x2000x850 |
Dimension WxHxD (mm) HPM module |
442xl 30(3U)x620 |
Net weight (kg) UPS cabinet |
170 / 230 / 260 / 280-470 / 650 / 720 |
Net weight (kg) HPM module |
32 |
|
|
STANDARDS |
|
Safety |
IEC/EN62040-1,IEC/EN60950-1 |
EMC |
IEC/EN62040-3,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
|
|