| Model Polaris BPM 150 |
|
| |
|
| Capacity |
50~150K/50~150K -- 50~200K/50~200K -- 50~300K/50~300K -- 50~400K/ 50~400K -- 50~500K/50~500K -- 50~600K/50~600K |
| |
|
| input |
|
| Nominal voltage |
380/400/41 SVac, (3Ph+N+PE) |
| Operating voltage range |
138~305Vac Linear derating; 305~485Vac for 100% Load; |
| Operating frequency range |
40Hz-70Hz |
| Power factor |
≥ 0.99 |
| Harmonic distortion (THDi) |
3% (100% linear load) |
| Bypass voltage range |
Max. voltage:220V: +250/o(optional + 10%,+ 15%,+20%); 230V: +20%(optional + 10%,+ 15%) ;240V: + 15%(optional + 10%) Min. voltage: -45% (optional-10%, -20%,-30%) |
| Bypass Frequency range |
Frequency protection range: ±10% |
| Generator input |
Support |
| |
|
| output |
|
| Rated voltage |
380/400/41 SVac, (3Ph+N+PE) |
| Power factor |
1 |
| Voltage regulation |
±1% |
| Output frequency Line Mode |
±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) |
| Output frequency Bat. Mode |
(50/60±0.1 %)Hz |
| Crest factor |
3:1 |
| Harmonic distortion (tdh) |
≤ 1 % with linear load / ≤4% with non linear load |
| Efficiency |
96,5% |
| |
|
| battery |
|
| Battery voltage |
Optional Voltage: ±180V/±192V/±204V/±216V/±228V/±240Vdc/±252Vdc/±264Vdc/±276Vdc/±288Vdc/±300Vdc (30/32/34/36/38/40/42/44/46/48/S0pcs) |
| Charge Current(A) UPS cabinet BPM150 Models150k/200K/300k/400k/500k/600k |
60A (Max.) / 80A (Max.) / 120A (Max.) / 160A (Max.) / 200A (Max.) / 240A (Max.) |
| Charge Current(A) HPM module |
20A (Max.) |
| |
|
| SYSTEM FEATURES |
|
| Transfer time |
Utility to Battery : 0ms; Utility to bypass: 0ms |
| Overload Line Mode |
110% for 60 min., 125% for 1 0min., 150% for 1 min, then transfer to bypass |
| Overload Bypass Mode |
≤135%@ ≤ 30șC or 125%@ ≤ 40șC:continuously, 1000% for 1 00ms, then shut down |
| Overheat |
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately |
| Low battery voltage |
Alarm and Switch off |
| Self-diagnostics |
Upon Power On and Software Control |
| EPO (optional) |
Shut down UPS immediately |
| Battery |
Advanced Battery Management |
| Noise suppression |
Complies with EN62040-3 |
| Audible & Visual alarms |
Line Failure, Battery Low, Overload, System Fault |
| Status LED & LCD display |
Line Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault |
| Reading on the LCD display |
lnput,Output, Battery, Command, Setting,Maintenace |
| Communication interface |
CAN, RS485,NET, Parallel, Dry contact port, Relay card (optional), SNMP card(optional),Battery temperature sentor (optional) |
| |
|
| ENVIRONMENTAL |
|
| Operating temperature |
0ºC ~ 40ºC |
| Storage temperature |
-25ºC ~ 55ºC |
| Humidity range |
0 ~ 95% (non condensing) |
| Altitude |
<1500m |
| Noise level (from 1M distance) |
<63dB / <65dB /<68dB / <70dB |
| |
|
| PHYSICAL |
|
| Dimension WxHxD (mm) UPS cabinet (SM) |
600x1200x850 / 600x1600x850 / 600x2000x850 / 600x2000x850 / 1200x2000x850 / 1400x 2000x850 |
| Dimension WxHxD (mm) UPS cabinet (FM) |
1200x2000x850 |
| Dimension WxHxD (mm) HPM module |
442xl 30(3U)x620 |
| Net weight (kg) UPS cabinet |
170 / 230 / 260 / 280-470 / 650 / 720 |
| Net weight (kg) HPM module |
32 |
| |
|
| STANDARDS |
|
| Safety |
IEC/EN62040-1,IEC/EN60950-1 |
| EMC |
IEC/EN62040-3,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
| |
|