Full specification
| Model Polaris HMP | |
| Capacity | 100 kva / 600 kva |
| input | |
| Tension | 400 Vac Three phase Vac |
| Voltage Tolerance | + 20% - 25% |
| frequency | 50/60 Hz autoranging |
| Frequency Tolerance | 45/65 Hz |
| Power Factor | 0,99 |
| Input Current | 141 a |
| Distortion current | <3% |
| Start ramp | 0-100% in 10 |
| output | |
| Number of phases | 3 + N |
| Crest Factor (lpeak / Irms) | 3 : 1 |
| Waveform | Sinusoidal |
| dynamic stability | ± 5% in 5 ms |
| frequency | As the input (auto sensing) |
| Voltage distortion with distorting load | <3% |
| Voltage distortion with linear load | <1% |
| Frequency Stability | ± 0.05% of principal fault ± 2% (selectable from ± 1% to ± 5% in the control panel) with mains present |
| overload | 125% 150% 200% to 10' / 1' / 7 |
| battery | |
| Type | sealed lead-acid maintenance free |
| Maximum current recharge | 0.2xC10 |
| by pass | |
| Tension evaluated | 400 Vac three-phase seleccionable 380 y 415 |
| Voltage Tolerance | ± 15% (selectable from ± 10% a ± 25% en el panel de control) |
| frequency evaluated | 50/60 Hz (auto sensing) |
| Frequency Tolerance | ± 2% (selectable from ± 1% a ± 5% en el panel de control) |
| current evaluated | 141 A |
| Number of phases | 3 |
| Backflow protection | yes |
| Overload capacity Inx10ms | 14 |
| environment | |
| maximum altitude | 1000 m |
| remotes | EPO y bypass |
| Safety Compliance | EN 62040-1 |
| EMC Compliance | EN 62040-2 Directivas 73/23-93/68-89/336 EEC EN 62040-3 |
| Degree of protection | 3 |
| Performance Line-Interactive / Smart Active | up to 98,5% |
| noise | 63 dBA to 1 m |
| remote signals | potential free contacts (mains failure, UPS on bypass, end of discharge pre-alarm, output 12Vdc 80mA) |
| Operating temperature | 0 ÷ 40 °C |
| relative humidity | 95% non-condensing |