Full specification

Model Polaris HMP  
   
Capacity 100 kva / 600 kva
   
input  
Tension 400 Vac Three phase Vac
Voltage Tolerance + 20% - 25%
frequency 50/60 Hz autoranging
Frequency Tolerance 45/65 Hz
Power Factor 0,99
Input Current 141 a
Distortion current <3%
Start ramp 0-100% in 10
   
output  
Number of phases 3 + N
Crest Factor (lpeak / Irms) 3 : 1
Waveform Sinusoidal
dynamic stability ± 5% in 5 ms
frequency As the input (auto sensing)
Voltage distortion with distorting load <3%
Voltage distortion with linear load <1%
Frequency Stability ± 0.05% of principal fault ± 2% (selectable from ± 1% to ± 5% in the control panel) with mains present
overload 125% 150% 200% to 10' / 1' / 7
   
battery  
Type sealed lead-acid maintenance free
Maximum current recharge 0.2xC10
   
by pass  
Tension evaluated 400 Vac three-phase seleccionable 380 y 415
Voltage Tolerance ± 15% (selectable from ± 10% a ± 25% en el panel de control)
frequency evaluated 50/60 Hz (auto sensing)
Frequency Tolerance ± 2% (selectable from ± 1% a ± 5% en el panel de control)
current evaluated 141 A
Number of phases 3
Backflow protection yes
Overload capacity Inx10ms 14
   
environment  
maximum altitude 1000 m
remotes EPO y bypass
Safety Compliance EN 62040-1
EMC Compliance EN 62040-2 Directivas 73/23-93/68-89/336 EEC EN 62040-3
Degree of protection 3
Performance Line-Interactive / Smart Active up to 98,5%
noise 63 dBA to 1 m
remote signals potential free contacts (mains failure, UPS on bypass, end of discharge pre-alarm, output 12Vdc 80mA)
Operating temperature 0 ÷ 40 °C
relative humidity 95% non-condensing