Full specification
| Model Polaris MP | |
| Capacity | 10 kva - 120 kVA |
| input | |
| Tension | three-phase with neutral [4 WIRE] |
| Voltage Tolerance | ± 20% A 100% loading ~ -40% +20% A 50% loading |
| Frequency Tolerance | ± 20% / 40 ~ 72 Hz |
| Power Factor | 0,99 |
| output | |
| active power | 10 KVA / 9000 W A 120 KVA / 108000 W |
| Output Current | 45 A [10 KVA] ~ 180 A [120 KVA] |
| Number of phases | 3 F + N |
| Crest Factor (lpeak / Irms) | 3 : 1 |
| Waveform | Sinusoidal |
| static stability | ± 0.5% |
| dynamic stability | ± 3% resistive load |
| frequency | 50/60 Hz selectable |
| Voltage distortion with distorting load | 3% |
| Voltage distortion with linear load | 1% |
| overload | 1´ / 5" / 0.5" para 133% / 150% / >150% respectively |
| battery | |
| type | sealed lead-acid maintenance free |
| Recharge time | 6 hours |
| by pass | |
| Tension evaluated | 230 Vca |
| Voltage Tolerance | ± 15% (selectable from ± 5% a ± 25% en el panel de control) |
| frequency evaluated | 50/60 Hz |
| Frequency Tolerance | ± 5% (selectable from ± 0,25% a ± 10%) |
| Number of phases | 1 |
| environment | |
| Degree of protection | 3 |
| Performance AC / AC | >94% |
| Performance Line-Interactive / Smart Active | >98% |
| noise | <48 dBA a 1 m |
| remote signals | free contacts |
| Operating temperature | 0 ÷ 40 °C |
| relative humidity | 95% non-condensing |