eficiencia

TAMAÑO
- ancho 440mm - alto 720mm - prof 86.5mm
tiempo tipico de recarga

productos relacionados
Especificación técnica
| Modelo Rt A 3000 HC | |
| POTENCIA | 3000VA/2700W |
| ENTRADA | |
| TENSION NOMINAL | 200/208/220/230/240VAC |
| RANGO DE TENSION DE OPERACION | |
| TRANSFERENCIA POR LINEA BAJA | 160VAC±5% @100%-80% LOAD; 140VAC±5% @80%-70% LOAD; 120VAC±5% @70%-60% LOAD; 110VAC±5% @60%-0% LOAD; (AMBIENT TEMP. <35°C) |
| RETORNO DE LINEA BAJA | 175VAC±5% @100%-80% LOAD; 155VAC±5% @80%-70% LOAD; 135VAC±5% @70%-60% LOAD; 12SVAC±5% @60%-0% LOAD; (AMBIENT TEMP. <35ºC) |
| TRANSFERENCIA POR LINEA ALTA | 300VAC±5% |
| RETORNO DE LINEA ALTA | 290VAC±5% |
| RANGO DE FRECUENCIA DE OPERACION | 40-70HZ |
| FACTOR DE POTENCIA | 0,99 100% CARGA (TENSION DE ENTRADA NOMINAL) |
| RANGO DE TENSION DE BYPASS | PUNTO DE TENSION ALTA DE BYPASS 230-264: AJUSTE ESTE PUNTO EN LA PANTALLA LCD DESDE 230VAC (POR DEFECTO A 264VAC) PUNTO DE TENSION BAJA DE BYPASS 170-220: AJUSTE ESTE PUNTO EN LA PANTALLA LCD DESDE 170 A 220 VAC (POR DEFECTO A 170VAC) |
| ENTRADA GENERADOR | SOPORTADA |
| SALIDA | |
| TENSION DE SALIDA | 220/208/220/230/240VAC |
| FACTOR DE POTENCIA | 0,9 |
| REGULACION DE VOLTAGE | ±1% |
| FRECUENCIA | |
| MODO LINEA (RANGO SINCRONIZADO) | 47-53HZ OR 57-63 HZ |
| MODO BATERIA | (50/60±0,1) HZ |
| FACTOR DE CRESTA | 3:1 |
| DISTRSION ARMONICA | ≤3% CON CARGAS NO LINEALES ≤6% CON CARGAS NO LINEALES |
| FORMA DE ONDA | SENOIDAL PURA |
| TIEMPO DE TRANSFERENCIA | |
| MODO AC < - > MODO BATERIA | ZERO |
| INVERSOR < - > BYPASS | 4MS (TIPICO) |
| EFICIENCIA | 92% (MODO AC) 90% (MODO DC) |
| BATERIA | |
| TIPO DE BATERIA | DEPENDE DE LA CONFIGURACION |
| NUMERO | DEPENDE DE LA CAPACIDAD DE LAS BATERIAS EXTERNAS |
| TIEMPO DE AUTONOMIA | PARA AUTONOMIAS LARGAS DEPENDE DE LA CAPACIDAD DE LAS BATERIAS EXTERNAS |
| TIEMPO TIPICO DE RECARGA | DEPENDE DE LA CAPACIDAD DE LAS BATERIAS EXTERNAS |
| TENSION DE CARGA | 82.1 VDC ±1% |
| CORRIENTE DE CARGA | 12A |
| CARACTERISTICAS DEL SISTEMA | |
| SOBRECARGA @35°c | 105% a 110%: LA UPS TRANSFIERE A BYPASS DESPUES DE 10 MINUTOS CUANDO LA RED ELECTRICA ESTA NORMAL, 110% a 130%: LA UPS TRANSFIERE A BYPASS DESPUES DE 1 MINUTO CUANDO LA RED ELECTRICA ESTA NORMAL, 130% a 150%: LA UPS TRANSFIERE A BYPASS DESPUES DE 5 SEGUNDOS CUANDO LA RED ELECTRICA ESTA NORMAL, 150%: LA UPS TRANSFIERE A BYPASS IMMEDIATAMENTE CUANDO LA RED ELECTRICA ESTA NORMAL, >130%: LA UPS TRANSFIERE A BYPASS IMMEDIATAMENTE CUANDO LA RED ELECTRICA ESTA NORMAL |
| CORTO CIRCUITO | SISTEMA EN ESPERA |
| SOBRECALENTAIENTO | MODO LINEA: CAMBIA A BYPASS; MODO RESPALDO: APAGA LA UPS DE INMEDIATO |
| BAJA TENSION DE BATERIA | ALARMA Y DESCONECTA |
| PARADA DE EMERGENCIA | APAGA DE INMEDIATO |
| ALARMAS SONORAS Y VISUALES | FALLO DE RED , BATERIA BAJA, SOBRECARGA, FALLA SISTEMA |
| INTERFACE DE COMUNICACION | USB (O RS232), TARJETA SNMP (OPCIONAL) TARJETA DE RELES (OPCIONAL) |
| AMBIENTAL | |
| TEMPERATURA DE OPERCION | 0°C ≈ 40°C |
| TEMPERATURA DE ALMACENAMIENTO | -25°C ≈ 55°C |
| RANGO DE HUMEDAD | 20-90 % RH @ 0-40°C (SIN CONDENSAR) |
| ALTITUD | <1500M |
| NIVEL DE RUIDO | MENOR A 50Dba a 1 metro |
| FISICAS | |
| DIMMENSIONES ANCHO X ALTO X PROFUNDIDAD (mm) | 440 X 720 X 86,5 |
| NORMAS | |
| SEGURIDAD | IEC/EN62040-1, IEC/EN60950-1 |
| EMC | IEC61000-4-5, IEC61000-4-6, IEC61000-4-8 |