Full specification

Model Rt A 3000 HC  
   
Capacity 3000VA/2700W
   
input  
NOMINAL VOLTAGE 200/208/220/230/240VAC
   
OPERATING VOLTAGE RANGE  
LOW LINE TRANSFER 160VACą5% @100%-80% LOAD; 140VACą5% @80%-70% LOAD; 120VACą5% @70%-60% LOAD; 110VACą5% @60%-0% LOAD; (AMBIENT TEMP. <35°C)
LOW LINE COMEBACK 175VACą5% @100%-80% LOAD; 155VACą5% @80%-70% LOAD; 135VACą5% @70%-60% LOAD; 12SVACą5% @60%-0% LOAD; (AMBIENT TEMP. <35şC)
HIGH LINE TRANSFER 300VACą5%
HIGH LINE COMEBACK 290VACą5%
   
OPERATING FREQUENCY RANGE 40-70HZ
POWER FACTOR 0,99 100% LOAD (NOMINAL INPUT VOLTAGE)
BYPASS VOLTAGE RANGE BYPASS HIGH VOLTAGE POINT 230-264: SETTING THE HIGH VOLTAGE POINT IN LCD FROM 230VAC (DEFAULT: 264 VAC) BYPASS LOW VOLTAGE POINT 170-220: SETTING THE LOW VOLTAGE POINT IN LCD FROM 170VAC TO 220VAC (DEFAULT: 170 VAC)
GENERATOR INPUT SUPPORT
   
output  
OUTPUT VOLTAGE 220/208/220/230/240VAC
POWER FACTOR 0,9
VOLTAGE REGULATION ±1%
   
FREQUENCY  
LINE MODE (SYNCHRONIZED RANGE) 47-53HZ OR 57-63 HZ
BAT. MODE (50/60ą0,1) HZ
   
CREST FACTOR 3:1
HARMONIC DISTORTION (THDC) ≤3% THDWITH LINEAR LOAD ≤6% THD WITH NON LINEAR LOAD
WAVEFORM PURE SINEWAVE
   
TRANSFER TIME  
AC MODE < - > BLAT. MODE ZERO
INVERTER < - > BYPASS 4MS (TYPICAL)
   
EFFICIENCY 92% (AC MODE) 90% (DC MODE)
   
battery  
BATTERY TYPE DEPENDS ON CONFIGURATION
NUMBERS DEPENDING ON THE CAPACITY OF EXTERNAL BATTERIES
BACKUP TIME LONG RUN UNIT DEPENDS ON THE CAPACITY OF EXTERNAL BATTERIES
TYPICAL RECHARGE TIME DEPENDING ON THE CAPACITY OF EXTERNAL BATTERIES
CHARGING VOLTAGE 82.1 VDC ą1%
CHARGE CURRENT 12A
   
SYSTEM FEATURES  
OVERLOAD @35°c 105%-110%: UPS TRANSFER TO BYPASS AFTER 10 MINUTES WHEN THE UTILITY IS NORMAL. 110%-130%: UPS TRANSFER TO BYPASS AFTER 1 MINUTE WHEN THE UTILITY IS NORMAL 130%-1S0%: UPS TRANSFER TO BYPASS AFTER S SECONDS WHEN THE UTILITY IS NORMAL 150%: UPS TRANSFER TO BYPASS IMMEDIATELY WHEN THE UTILITY IS NORMAL 35'C130%: UPS TRANSFER TO BYPASS IMMEDIATELY WHEN THE UTILITY IS NORMAL
SHORT CIRCUIT HOLD WHOTE SYSTEM
OVERHEAT LINE MODE: SWITCH TO BYPASS; BACKUP MODE: SHUT DOWN UPS IMMDIATELY
LOW BATTERY VOLTAGE ALARM ANO SWITCH OFF
EPO (OPTIONAL) SHUT DOWN UPS IMMEDIATELY
AUDIBLE & VISUAL ALARMS LINE FAILURE , BATTERY LOW, OVERLOAD, SYSTEM FAULT
COMUINICATION INTERFACE USB (OR RS232), SNMPCARD (OPTIONAL), RELATY CARO (OPTIONAL)
   
ENVIRONMENTAL  
OPERATING TEMPERATURE 0°C ≈ 40°C
STORAGE TEMPERATURE -25°C ≈ 55°C
HUMIDITY RANGE 20-90 % RH @ 0-40°C (NON-CONDENSING)
ALTITUDE <1500M
NOISE LEVEL LESS THAN 50DBA AT 1 METER
   
PHYSICAL  
DIMENSION W X H X D (MM) 440 X 720 X 86,5
   
STANDARDS  
SAFEATY IEC/EN62040-1, IEC/EN60950-1
EMC IEC61000-4-5, IEC61000-4-6, IEC61000-4-8