efficiency

size
- W 440mm - H 720mm - D 86,5mm
typical recharging time

Related products
Full specification
| Model Rt A 3000 HC | |
| Capacity | 3000VA/2700W |
| input | |
| NOMINAL VOLTAGE | 200/208/220/230/240VAC |
| OPERATING VOLTAGE RANGE | |
| LOW LINE TRANSFER | 160VACą5% @100%-80% LOAD; 140VACą5% @80%-70% LOAD; 120VACą5% @70%-60% LOAD; 110VACą5% @60%-0% LOAD; (AMBIENT TEMP. <35°C) |
| LOW LINE COMEBACK | 175VACą5% @100%-80% LOAD; 155VACą5% @80%-70% LOAD; 135VACą5% @70%-60% LOAD; 12SVACą5% @60%-0% LOAD; (AMBIENT TEMP. <35şC) |
| HIGH LINE TRANSFER | 300VACą5% |
| HIGH LINE COMEBACK | 290VACą5% |
| OPERATING FREQUENCY RANGE | 40-70HZ |
| POWER FACTOR | 0,99 100% LOAD (NOMINAL INPUT VOLTAGE) |
| BYPASS VOLTAGE RANGE | BYPASS HIGH VOLTAGE POINT 230-264: SETTING THE HIGH VOLTAGE POINT IN LCD FROM 230VAC (DEFAULT: 264 VAC) BYPASS LOW VOLTAGE POINT 170-220: SETTING THE LOW VOLTAGE POINT IN LCD FROM 170VAC TO 220VAC (DEFAULT: 170 VAC) |
| GENERATOR INPUT | SUPPORT |
| output | |
| OUTPUT VOLTAGE | 220/208/220/230/240VAC |
| POWER FACTOR | 0,9 |
| VOLTAGE REGULATION | ±1% |
| FREQUENCY | |
| LINE MODE (SYNCHRONIZED RANGE) | 47-53HZ OR 57-63 HZ |
| BAT. MODE | (50/60ą0,1) HZ |
| CREST FACTOR | 3:1 |
| HARMONIC DISTORTION (THDC) | ≤3% THDWITH LINEAR LOAD ≤6% THD WITH NON LINEAR LOAD |
| WAVEFORM | PURE SINEWAVE |
| TRANSFER TIME | |
| AC MODE < - > BLAT. MODE | ZERO |
| INVERTER < - > BYPASS | 4MS (TYPICAL) |
| EFFICIENCY | 92% (AC MODE) 90% (DC MODE) |
| battery | |
| BATTERY TYPE | DEPENDS ON CONFIGURATION |
| NUMBERS | DEPENDING ON THE CAPACITY OF EXTERNAL BATTERIES |
| BACKUP TIME | LONG RUN UNIT DEPENDS ON THE CAPACITY OF EXTERNAL BATTERIES |
| TYPICAL RECHARGE TIME | DEPENDING ON THE CAPACITY OF EXTERNAL BATTERIES |
| CHARGING VOLTAGE | 82.1 VDC ą1% |
| CHARGE CURRENT | 12A |
| SYSTEM FEATURES | |
| OVERLOAD @35°c | 105%-110%: UPS TRANSFER TO BYPASS AFTER 10 MINUTES WHEN THE UTILITY IS NORMAL.
110%-130%: UPS TRANSFER TO BYPASS AFTER 1 MINUTE WHEN THE
UTILITY IS NORMAL
130%-1S0%: UPS TRANSFER TO BYPASS AFTER S SECONDS WHEN THE UTILITY IS NORMAL
150%: UPS TRANSFER TO BYPASS IMMEDIATELY WHEN THE UTILITY
IS NORMAL
35'C |
| SHORT CIRCUIT | HOLD WHOTE SYSTEM |
| OVERHEAT | LINE MODE: SWITCH TO BYPASS; BACKUP MODE: SHUT DOWN UPS IMMDIATELY |
| LOW BATTERY VOLTAGE | ALARM ANO SWITCH OFF |
| EPO (OPTIONAL) | SHUT DOWN UPS IMMEDIATELY |
| AUDIBLE & VISUAL ALARMS | LINE FAILURE , BATTERY LOW, OVERLOAD, SYSTEM FAULT |
| COMUINICATION INTERFACE | USB (OR RS232), SNMPCARD (OPTIONAL), RELATY CARO (OPTIONAL) |
| ENVIRONMENTAL | |
| OPERATING TEMPERATURE | 0°C ≈ 40°C |
| STORAGE TEMPERATURE | -25°C ≈ 55°C |
| HUMIDITY RANGE | 20-90 % RH @ 0-40°C (NON-CONDENSING) |
| ALTITUDE | <1500M |
| NOISE LEVEL | LESS THAN 50DBA AT 1 METER |
| PHYSICAL | |
| DIMENSION W X H X D (MM) | 440 X 720 X 86,5 |
| STANDARDS | |
| SAFEATY | IEC/EN62040-1, IEC/EN60950-1 |
| EMC | IEC61000-4-5, IEC61000-4-6, IEC61000-4-8 |